Ubicación: Global + English
Global Global Algérie Français Algeria English Angola Português Angola English Argentina Español Argentina English Australia English Austria Deutsch Austria English Azerbaijan English Azerbaijan Русский Bahrain English Bangladesh English Belgium English Belgium Français Belgium Nederlands Brazil Português Brazil English Bulgaria български Bulgaria English Cameroon English Cameroon Français Canada English Canada Français Chile Español Chile English China 中文 China 日本語 China English Colombia Español Colombia English Croatia English Czech Republic Čeština Czech Republic English Denmark English Djibouti English Ecuador Español Ecuador English Egypt English Estonia English Ethiopia English Finland Suomi Finland English France Français France English Georgia English Georgia Русский Germany Deutsch Germany English Ghana English Greece Ελληνικά Greece English Guatemala Español Guatemala English Hong Kong, China English Hong Kong, China 中文 Hungary Magyar Hungary English India English Indonesia English Iraq English Ireland English Italy Italiano Italy English Ivory Coast Français Ivory Coast English Japan 日本語 Japan English Jordan English Kazakhstan Русский Kazakhstan English Kenya English Kuwait English Kyrgyzstan Русский Kyrgyzstan English Latvia English Lithuania English Malaysia English Mauritius English Mauritius français (Maurice) Mexico Español Mexico English Moldova Română Moldova English Mongolia English Morocco English Morocco Français Mozambique Português Mozambique English Netherlands Nederlands Netherlands English New Zealand English Nigeria English Norway English Oman English Pakistan English Paraguay Español Paraguay English Peru Español Peru English Philippines English Poland Polski Poland English Portugal Português Portugal English Qatar English Republic of Korea 한국어 Republic of Korea English Romania Română Romania English Saudi Arabia English Serbia Српски Serbia English Singapore English Slovakia English Slovenia English South Africa English Spain English Spain Español Sri Lanka English Sweden English Switzerland Deutsch Switzerland Français Switzerland Italiano Switzerland English Tanzania English Thailand ไทย Thailand English Togo English Togo Français Tunisia English Tunisia Français Türkiye Türkçe Türkiye English Turkmenistan Русский Turkmenistan English Ukraine Українська Ukraine English United Arab Emirates English United Kingdom English Uruguay Español Uruguay English USA English Uzbekistan English Uzbekistan Русский Vietnam Tiếng Việt Vietnam English

Plastic combustion performance classification is a critical fire-safety evaluation that determines how polymeric materials ignite, burn, and drip when exposed to a flame source. This article provides a comprehensive analysis of the major flammability rating systems—including UL 94, GB/T 2408, IEC 60695, ISO 4589, and GB 8624—covering test samples, testing items, methods, and typical applications. Understanding these classifications helps manufacturers select compliant materials for electronics, automotive, construction, and appliance applications.

Technical Overview

Plastics are organic polymeric materials that are inherently combustible, making flammability assessment essential for product safety, regulatory compliance, and material selection. Combustion performance classification evaluates characteristics such as ignitability, burning rate, afterflame time, afterglow, flaming drips, and smoke generation under controlled laboratory conditions.

The most widely used classification frameworks for plastics include:

  • UL 94 – The dominant flammability standard from the United States, defining ratings such as HB, V-0, V-1, V-2, 5VA, and 5VB for solid plastics, plus VTM and HF classes for thin films and foams.
  • GB/T 2408 – The Chinese national standard for horizontal and vertical burning, technically aligned with IEC 60695-11-10 and IEC 60695-11-20.
  • ISO 1210 / IEC 60695-11 series – International standards equivalent to UL 94 small-flame testing methods.
  • GB/T 2406 / ISO 4589 / ASTM D2863 – Limiting oxygen index (LOI) methods that quantify the minimum oxygen concentration required to sustain burning.
  • GB 8624 / EN 13501-1 – Combustion performance classification for construction products, including plastic building materials.

From lowest to highest flame retardance, the commonly referenced hierarchy for engineering plastics is: HB < V-2 < V-1 < V-0 < 5VB < 5VA. Materials with a limiting oxygen index of 27% or higher are generally considered self-extinguishing or flame-retardant.

Testing Samples

Molded and Cut Bar Specimens

For horizontal (HB) and vertical (V-0/V-1/V-2) burning tests, standard bar specimens measuring 125 mm × 13 mm are used, typically tested at two or more thicknesses such as 0.8 mm, 1.5 mm, 3.0 mm, and 6.0 mm. Specimens may be injection molded, compression molded, or cut from sheets, and the edges should be smooth and free of burrs. Each vertical burning test generally requires two sets of five specimens.

Plaque Specimens for 5VA and 5VB

The 500 W vertical burning test (IEC 60695-11-20) requires both bar specimens (125 mm × 13 mm) and horizontal plaques of approximately 150 mm × 150 mm. The plaque test evaluates whether the material can be burned through, distinguishing 5VA (no burn-through hole) from 5VB (burn-through permitted).

Thin Films and Flexible Materials

Films thinner than 0.25 mm are classified under the VTM-0, VTM-1, or VTM-2 categories using rolled or mandrel-supported specimens. Oxygen index testing of films requires special framing holders to keep the specimen self-supporting during the test.

Foamed Materials

Cellular plastics are classified as HBF, HF-1, or HF-2 using specimen dimensions of 125 mm × 50 mm, evaluated for burning rate, afterflame time, and ignition of an underlying cotton indicator by flaming drips.

Finished Parts and Components

End-product enclosures, connectors, terminal blocks, and decorative parts may be assessed directly for glow-wire, needle-flame, or finished-product-level flammability requirements defined in product safety standards.

Testing Items

Common combustion performance testing items for plastic materials include:

  • Horizontal burning test (HB classification, burning rate in mm/min)
  • Vertical burning test at 20 mm flame height (V-0, V-1, V-2 classifications)
  • 500 W vertical burning test (5VA and 5VB classifications)
  • Thin-film vertical burning (VTM-0, VTM-1, VTM-2)
  • Foam material horizontal burning (HBF, HF-1, HF-2)
  • Limiting oxygen index (LOI, % O₂)
  • Glow-wire ignition temperature (GWIT) and glow-wire flammability index (GWFI)
  • Needle-flame test
  • Smoke density and specific optical density
  • Heat release rate and total heat release (cone calorimetry)
  • Building product classification per GB 8624 or EN 13501-1 (A1/A2/B/C/D/E/F)

Testing Methods

Horizontal Burning Test (HB)

Conducted per UL 94 HB, ASTM D635, GB/T 2408, or IEC 60695-11-10, a 20 mm blue flame from a calibrated burner is applied at a 45° angle to one end of a horizontally clamped specimen for 30 seconds. The material is classified HB if burning ceases before the 100 mm mark or if the measured burning rate does not exceed 40 mm/min for thicknesses of 3.0 to 13 mm, or 75 mm/min for thicknesses below 3.0 mm.

Vertical Burning Test (V-0, V-1, V-2)

Performed per UL 94, GB/T 2408, IEC 60695-11-10, or ISO 1210, the specimen is clamped vertically and exposed to a 20 mm flame applied twice for 10 seconds each. Classifications are based on afterflame time after each application, total afterflame time across all ten applications, afterglow duration, and whether flaming drips ignite surgical cotton placed below the specimen. V-0 requires individual afterflame times of 10 seconds or less and a total of 50 seconds or less with no flaming drips; V-1 permits afterflame times up to 30 seconds without flaming drips; V-2 allows the same timing limits as V-1 but tolerates flaming drips that ignite the cotton.

500 W Vertical Burning Test (5VA, 5VB)

Following IEC 60695-11-20, UL 94, or GB/T 2408, a higher-energy 125 mm flame is applied five times for 5 seconds each to bar and plaque specimens. Both 5VA and 5VB require no flaming drips and no ignition of the cotton indicator. A material qualifies as 5VA if the plaque is not burned through, while 5VB permits a burn-through hole in the plaque. These are the most severe small-flame classifications and are frequently specified for enclosures of fire enclosures in IT equipment.

Limiting Oxygen Index (LOI)

Per GB/T 2406.2, ISO 4589-2, and ASTM D2863, a vertically mounted specimen is ignited in a glass chimney through which a controlled mixture of oxygen and nitrogen flows. The oxygen concentration is adjusted to determine the minimum level that just sustains candle-like burning for 3 minutes or over a 50 mm distance. Typical interpretation: LOI below 21% indicates a readily combustible material, 21–26% combustible, above 27% generally self-extinguishing, and above 32% considered difficult to ignite.

Glow-Wire Tests

Based on IEC 60695-2-10 through IEC 60695-2-13, a nickel-chromium glow wire heated to temperatures of 550 °C, 650 °C, 750 °C, 850 °C, or 960 °C is pressed against the specimen for 30 seconds. The glow-wire flammability index (GWFI) records the highest temperature at which the specimen either does not ignite or self-extinguishes within 30 seconds without igniting tissue paper below. The glow-wire ignition temperature (GWIT) is the temperature 25 K (or 30 K) above the highest temperature at which ignition does not occur during three consecutive tests.

Needle-Flame Test

Described in IEC 60695-11-5, this test applies a small 12 mm flame from a needle burner to simulate fault conditions caused by small flames or glowing elements. Pass criteria depend on afterflame time, whether burning drips ignite tissue paper, and whether a pine board beneath the specimen is charred.

Smoke Density and Heat Release

Smoke generation is measured using the NBS smoke chamber method (ASTM E662 or GB/T 8323), which records specific optical density. Heat release behavior is characterized by cone calorimetry per ISO 5660 or GB/T 16172, providing data on peak heat release rate, total heat release, and smoke production rate. These results are particularly relevant for classification under GB 8624 and EN 13501-1 for construction applications.

Applications

Electrical and Electronic Products

Enclosures, PCBs, connectors, switches, and power adapters for IT equipment, chargers, and household appliances typically require V-0 at the minimum relevant thickness, while fire enclosures may demand 5VA. Glow-wire performance (GWFI 960 °C, GWIT 775/800 °C) is commonly specified for unattended appliances under IEC 60335-1.

Automotive and Rail Transit

Interior trim, cable jackets, battery components, and structural parts must satisfy horizontal burning, vertical burning, or LOI requirements defined by OEM specifications and industry standards. Rail applications impose strict limits on smoke density and toxic gas emission alongside flame spread.

Building and Construction Materials

Pipes, insulation foams, wall panels, roofing membranes, and decorative materials must be classified under GB 8624 (grades A, B1, B2, B3) or EN 13501-1 (Euroclasses A1 to F), depending on the market, often supported by cone calorimeter and SBI (single burning item) test data.

Home Appliances and Consumer Goods

Plastic housings for heaters, kitchen appliances, luminaires, and power tools are evaluated for glow-wire, needle-flame, and UL 94 performance to satisfy product safety standards such as IEC 60335, IEC 60598, and IEC 62368-1.

Wire and Cable

Insulation and sheathing compounds are assessed through LOI, vertical tray flame tests, and smoke emission tests to verify flame-retardant, low-smoke, and halogen-free performance claims.

FAQ

What is the difference between V-0, V-1, and V-2?

All three are vertical burning classifications. The differences lie in afterflame time and flaming drips: V-0 requires afterflame times of 10 seconds or less per application with no flaming drips; V-1 allows up to 30 seconds per application with no flaming drips; V-2 also allows up to 30 seconds but tolerates flaming drips that ignite the cotton indicator.

Are UL 94 and GB/T 2408 ratings interchangeable?

The test methods and pass criteria in GB/T 2408 are technically aligned with IEC 60695-11-10 and IEC 60695-11-20, which correspond to UL 94 V and 5V methods. In practice, however, the issuing body, certification context, and market acceptance differ, so manufacturers should confirm which report or certification scheme their target market and product standard require.

Why must flammability ratings be reported with a thickness?

Flame retardance is thickness-dependent: thinner sections ignite more easily and burn longer. A material rated V-0 at 3.0 mm may only achieve V-1 or V-2 at 1.5 mm. Ratings are therefore always expressed with the tested minimum thickness, and the thinnest wall section of the final part governs compliance.

How does the oxygen index relate to UL 94 ratings?

LOI is a quantitative screening parameter, while UL 94 is a pass/fail classification. As a general guideline, materials with an LOI above 27% tend to achieve V-0, those between 22% and 27% often reach V-1 or V-2, and those below 21% typically fall into the HB category. However, the two results are not directly convertible because dripping behavior and specimen geometry strongly influence UL 94 outcomes.

Which classification applies to plastic building materials?

Plastic products used in construction in China are classified under GB 8624-2012 as A (non-combustible), B1 (difficult to ignite), B2 (combustible), or B3 (readily combustible). In Europe, the equivalent system is EN 13501-1 with Euroclasses A1, A2, B, C, D, E, and F, supported by tests such as the single burning item test and cone calorimetry.

How should specimens be conditioned before testing?

Unless otherwise specified, specimens are conditioned at 23 ± 2 °C and 50 ± 5% relative humidity for at least 48 hours prior to testing. For certain hygroscopic or flame-retardant compounds, additional pre-drying is required to ensure reproducible results. Accredited third-party laboratories follow the conditioning requirements stated in each standard to guarantee the validity of reported classifications.